Designed
with low cost and portability in mind, the use of the 2080
provides on or off site verification of RCD Testers, LOOP
Testers, Continuity and Insulation Testers.
The 2080 is simple to use and provides the following functionality:
Checking
of Insulation Testers
3 high value resistors (1M Ohms, 9.9M Ohms & 99M Ohms) for testing
the resistance measurement function.
LED indication of test voltage at 100V 250V
500V 1000V
3 low value resistors ( 0.5 Ohms, 2 Ohms & 10 Ohms) for testing
the continuity function.
AC line voltage output for testing voltage measurement
Checking
of RCD Testers
Dedicated 13A socket provides functional check of RCD tester
operation
3 selectable ranges : 10mA@150ms 30mA@150ms
150mA@30ms
Indicators for Ready
Tripped
Overcurrent
Checking
of LOOP Testers
A
functional check of LOOP Testers, allowing direct measurement
of supplied loop impedance and supplied loop impedance + 1 Ohms
via a dedicated 13A socket.
Wiring
Check
When
connected, the 2080 checkbox will indicate voltage between
the following wires *
P-E (Phase to Earth)
P-N (Phase to Neutral)
N-E (Neutral to
Earth)
* Does not detect Neutral to Earth
reversal
Certification
Calibration
Certificates traceable to UK National Standards or UKAS are
available.
| Back to top |
 |
|